Transmitter MP 26 Seite / page 2
PArA
M Input
Name Value range Description
InL.1 -1999...9999 Input value for the lower scaling point
OuL.1 -1999...9999 Displayed value for the lower scaling point
InH.1 -1999...9999 Input value for the upper scaling point
OuH.1 -1999...9999 Displayed value for the lower scaling point
t.F1 0...999,9 Filter time constant [s]
b.F1 0...9999 Filter bandwidth
Lim
Name Value range Description
L.1 -1999...9999 Lower limit 1 (L.1< -1999 =off)
H.1 -1999...9999 Upper limit 1 (H.1< -1999 =off)
HYS.1 0...9999 Hysteresis limit 1
L.2 -1999...9999 Lower limit 2 (L.2< -1999 =off)
H.2 -1999...9999 Upper limit 2 (H.2< -1999 =off)
HYS.2 0...9999 Hysteresis limit 2
L.3 -1999...9999 Lower limit 3 (L.3< -1999 =off)
H.3 -1999...9999 Upper limit 3 (H.3< -1999 =off)
HYS.3 0...9999 Hysteresis limit 3
ConF
Func
Name Value
range Description
Fnc.1 Function 1
0no function
1Reset to zero
Fnc.2 Function 2
0no function
3tara-function
M Input
Name Value
range Description
S.tYP Sensor type selection
60 0,5 mV/V
61 1 mV/V
62 2 mV/V
63 4 mV/V (3,33 mV/V)
S.Lin Linearization
0none
1Linearization to specification. Creation of lineariza-
tion table with (engineering tool MP26/10) possible.
In.F OFF,
-1999...
9999
Alternative value for M
Lim
Name Value
range Description
Fnc.1
(Fnc.2)
(Fnc.3)
Function of limit 1 (2,3)
0switched off
1measured value monitoring
2Measured value monitoring + alarm status storage.
A stored limit value can be reset via error list or a digi-
tal input ( -> LOGI/ Err.r)
Src.1
(Src.2)
(Src.3)
Source of limit 1 (2,3)
0process value = Absolute alarm
3measured value M
Out.1,Out.2 and Out3
Name Value range Description
O.tYP Signal type selection OUT3 only
10 ... 20 mA continuous
24 ... 20 mA continuous
30...10 V continuous
42...10 V continuous
O.Act Method of operation of output OUT1, 2 or 3
0direct / normally open
1inverse / normally closed
Lim.1 Limit 1 signal
0not active
1active
Lim.2 Limit 2 signal
0not active
1active
Lim.3 Limit 3 signal
0not active
1active
FAi.1 M error
0not active
1active
Out.0 -1999
...9999 Scaling of the analog output for 0% (0/4mA or 0/2V)
Out.1 -1999
...9999 Scaling of the analog output for 100% (20mA or
10V)
O.Src Signal source of the analog output OUT3
0not active
3process value
7measured value M
O.FAI Fail behaviour
0upscale
1downscale
LOGI
Name Value
range Description
di.Fn Function of digital inputs (valid for all inputs)
0direct
1invers
2toggle key function (adjustable for 2-point-operation
with interface and di1)
L_r Local / Remote switching (Remote: adjusting of all
values by front keys is blocked)
1always active
2Di1 switches
7limit 1 switches
8limit 2 switches
9limit 3 switches
Err.r Reset of all error list entries
2Di1 switches
7limit 1 switches
8limit 2 switches
9limit 3 switches
10 Enter/INC switches
11 Enter/DEC switches
tArA Tare-function
2Di1 switches
7limit 1 switches
8limit 2 switches
9limit 3 switches
10 Enter/INC switches
11 Enter/DEC switches
rES.L Reset minimum value
2Di1 switches
7limit 1 switches
8limit 2 switches
9limit 3 switches
10 Enter/INC switches
11 Enter/DEC switches
Name Value
range Description
rES.H Reset maximum value
2Di1 switches
7limit 1 switches
8limit 2 switches
9limit 3 switches
10 Enter/INC switches
11 Enter/DEC switches
ZEro Reset to zero
2Di1 switches
7limit 1 switches
8limit 2 switches
9limit 3 switches
10 Enter/INC switches
11 Enter/DEC switches
othr
Name Value
range Description
FrEq switch power frequency 50Hz/60Hz
0power frequency 50Hz
1power frequency 60Hz
D.Unt Display unit (presentation on the display)
19 kg
20 g
21 t
22 Text of physical unit (preset by T.Unit) µ
23 lb
dP Decimal point (max. number of digits behind decimal point)
0no digit behind the decimal point
11 digit behind the decimal point
22 digits behind the decimal point
33 digits behind the decimal point
µSettings for text in display 2 (max. 5 digits; only visible with Engineering Tool
MP26/10) !
+Depending on equipment version and the configuration unused parameters
are faded out.