WIKA FSD-3 Bedienungsanleitung

Typ
Bedienungsanleitung
Operating instructions
Betriebsanleitung
Mode d'emploi
Manual de instrucciones
EN
DE
FR
ES
Strömungsschalter, Typ FSD-3
Flow switch, model FSD-3
Flow switch, model FSD-3
Capteur de débit, type FSD-3
Detector de caudal, modelo FSD-3
2 WIKA operating instructions ow switch, model FSD-3
EN
DE
14153887.02 08/2017 EN/DE/FR/ES
FR
ES
© 09/2016 WIKA Alexander Wiegand SE & Co. KG
All rights reserved. / Alle Rechte vorbehalten.
WIKA
®
is a registered trademark in various countries.
WIKA
®
ist eine geschützte Marke in verschiedenen Ländern.
Prior to starting any work, read the operating instructions!
Keep for later use!
Vor Beginn aller Arbeiten Betriebsanleitung lesen!
Zum späteren Gebrauch aufbewahren!
Lire le mode d‘emploi avant de commencer toute opération !
A conserver pour une utilisation ultérieure !
¡Leer el manual de instrucciones antes de comenzar cualquier trabajo!
¡Guardar el manual para una eventual consulta!
Betriebsanleitung Typ FSD-3 Seite 35 - 66
Operating instructions model FSD-3 Page 3 - 34
Mode d‘emploi type FSD-3 Page 67 - 98
Manual de instrucciones modelo FSD-3 Page 99-131
3WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
Contents
Declarations of conformity can be found online at www.wika.com
Contents
1. General information 4
2. Design and function 5
3. Safety 7
4. Transport, packaging and storage 10
5. Commissioning, operation 11
6. Faults 22
7. Maintenance and cleaning 24
8. Dismounting, return and disposal 25
9. Specications 27
10. Accessories and spare parts 32
4 WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
1. General information
1. General information
The instrument described in the operating instructions has been designed and manufactured using state-of-the-
art technology. All components are subject to stringent quality and environmental criteria during production. Our
management systems are certied to ISO 9001 and ISO 14001.
These operating instructions contain important information on handling the instrument. Working safely requires that
all safety instructions and work instructions are observed.
Observe the relevant local accident prevention regulations and general safety regulations for the instrument’s range
of use.
The operating instructions are part of the product and must be kept in the immediate vicinity of the instrument and
readily accessible to skilled personnel at any time. Pass the operating instructions on to the next operator or owner
of the instrument.
Skilled personnel must have carefully read and understood the operating instructions prior to beginning any work.
The general terms and conditions contained in the sales documentation shall apply.
Subject to technical modications.
Further information:
- Internet address: www.wika.de / www.wika.com
- Relevant data sheet: FL 80.01
- Application consultant: Tel.: +49 9372 132-8976
Fax: +49 9372 132-8008976
5WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
2. Design and function
2. Design and function
2.1 Overview
Display and control panel
Electrical connection
Installation mark
Process connection, spanner flats
Probe
6 WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
2.2 Functional description
The ow switch works by the calorimetric principle and is used to convert the ow rate into an electric signal. The
instrument shows the ow rate in per cent on the digital display.
Optionally, the instrument measures the medium temperature.
The instrument can output up to 2 output signals as parameterised.
Switching signal for ow limit values
Switching signal for temperature limit values
Switching signal for diagnostic function
Analogue signal ow
Analogue signal temperature
2.3 Scope of delivery
Flow switch
Operating instructions
Accessories process connection (optional)
Further certicates (optional)
Cross-check scope of delivery with delivery note.
2. Design and function
7WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
3. Safety
3. Safety
3.1 Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result in serious injury or death, if not avoided.
CAUTION!
... indicates a potentially dangerous situation that can result in light injuries or damage to equipment or
the environment, if not avoided.
Information
... points out useful tips, recommendations and information for ecient and trouble-free operation.
3.2 Intended use
The ow switch has been designed and built solely for the intended use described here, and may only be used
accordingly.
Conversion of ow rates into an electric signal.
No assembly in downpipes open towards the bottom.
Use in buildings and outdoors (avoid high ambient temperatures and direct UV irradiation).
Ambience with max. pollution degree of 3.
Voltage supply of overvoltage category II.
Ambient temperature between -20 ... +80 °C.
Medium temperature between -20 ... +85 °C.
Relative humidity between 45 ... 75 % r. h.
Use for commercial purposes in industrial environment.
8 WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
3. Safety
The ow switch is used for monitoring ow losses and dry run. With analogue signal the ow switch should only be
used as a trend indicator, in order to monitor process changes, such as lter blocking.
Only use the ow switch in applications that lie within its technical performance limits.
→ For performance limits see chapter 9 “Specications”.
Refrain from unauthorised modications to the ow switch.
Any use beyond or dierent to the intended use is considered as improper use.
The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use.
3.3 Personnelqualication
Skilled personnel
Skilled personnel, authorised by the operator, are understood to be personnel who, based on their technical training,
knowledge of measurement and control technology and on their experience and knowledge of country-specic regula-
tions, current standards and directives, are capable of carrying out the work described and independently recognising
potential hazards.
Special operating conditions require further appropriate knowledge, e.g. of aggressive media.
9WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
3.4 Labelling, safety marks
Product label
If the serial number becomes illegible due to mechanical damage or overpainting, traceability will no longer be possible.
S# Serial no.
Pin assignment (incl. specications)
P# Product no.
Approvals
Measuring range (temperature)
Coded date of manufacture
Measuring range (ow)
Max. pressure limitation
Before mounting and commissioning the instrument, ensure you read the operating instructions!
DC voltage
3. Safety
10 WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
4. Transport, packaging and storage
4. Transport, packaging and storage
4.1 Transport
Check the ow switch for any damage that may have been caused by transport.
Obvious damage must be reported immediately.
4.2 Packaging and storage
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport (e.g. change in installation site, sending for
repair).
Permissible conditions at the place of storage:
Storage temperature: -20 ... +80 °C
Humidity: 45 ... 75 % relative humidity (no condensation)
Avoid exposure to the following factors:
Direct sunlight or proximity to hot objects
Mechanical vibration, mechanical shock (putting it down hard)
Soot, vapour, dust and corrosive gases
Humid or wet environment
Hazardous environments, ammable atmospheres
11WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
5. Commissioning, operation
5. Commissioning, operation
5.1 Mechanical mounting
Only use the ow switch if it is in perfect condition with respect to safety.
Prior to commissioning, the ow switch must be subjected to a visual inspection.
Commissioning and operation of the instrument may only be carried out by skilled personnel, see chapter 3.3 “Person-
nel qualication”.
5.1.1 Requirements for mounting point
The mounting position and probe length are extremely important for the quality and reliability of the measuring results.
The mounting point must meet the following conditions:
Sealing faces are clean and undamaged.
Sucient space for a safe electrical installation.
For information on tapped holes and welding sockets, see
Technical information IN 00.14 at www.wika.com.
Permissible ambient and medium temperatures remain
within the performance limits. Consider possible restric-
tions on the ambient temperature range caused by mating
connector used.
→ For performance limits see chapter 9 “Specications”
The probe tip must be completely surrounded by medium.
Position the probe tip in the area of maximum ow rate
(pipe centre).
The minimum immersion depth of the probe is L ≥16 mm.
The probe tip must not touch the opposite wall.
Air
Medium
Deposits
12 WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
5.1.2 Recommended mounting positions
Horizontal pipes
Only if the pipeline is free from
deposits.
Only if the pipeline is completely lled
with medium.
Risers and vertical pipes
Mounting the ow switch in downpipes open towards the bottom is forbidden. This use does not comply with the intended use.
5. Commissioning, operation
13WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
5.1.3 Probe alignment
During mechanical assembly of the FSD-3, make sure
that the installation mark points in the opposite direction
of the ow direction of the medium.
5.1.4 Sealing
For sealing the process connections with parallel
threads, use at gaskets, lens-type sealing rings or WIKA
prole sealings at the sealing face. With a tapered thread
(e.g. NPT thread), sealing is made in the thread using
additional sealing materials, e.g. PTFE tape (EN 837-2).
For further information on seals see WIKA
data sheet AC 09.08 or at www.wika.com.
5.1.5 Disturbing interferences in the piping system
For correct measurement, the ow switch requires a fully
characterised ow prole. This is why calming sections
must be provided in the pipeline after a pump, a pipe
elbow, installed parts and changes in cross-section.
Installation
mark
L > 3 ... 5 x D
L > 3 ... 5 x D
5. Commissioning, operation
14 WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
5.1.6 Mounting the instrument
The max. torque depends on the mounting point (e.g. material and shape). If you have any questions,
please contact our application consultant.
→ For contact details see chapter 1 “General information” or the back page of the operating instructions.
If a process connection adapter (optional) is used, rst screw it into the mounting point by hand and then tighten it
using a torque spanner. Use enclosed sealing.
1. Depressurise the system and switch o the ow.
2
.
Seal the process connection (→ see “Sealing variants”).
3
.
At the mounting point, screw the ow switch in hand-tight.
4
.
Tighten with a torque spanner using the spanner ats.
5.2 Electrical mounting
Requirements for voltage supply
Power supply: DC 15 ... 35 V
The power supply for the ow switch must be made via an energy-limited electrical circuit in accordance with section
9.3 of UL/EN/IEC 61010-1 or an LPS to UL/EN/IEC 60950-1 or class 2 in accordance with UL1310/UL1585 (NEC or
CEC). The voltage supply must be suitable for operation above 2,000 m above sea level, should the ow switch be
used at this altitude.
Requirement for shielding and grounding
The ow switch must be shielded and grounded in accordance with the grounding concept of the plant.
The instrument must be grounded via the process connection.
Connecting the instrument
1. Assemble the mating connector.
→ see pin assignment
2
.
Establish the plug connection.
5. Commissioning, operation
15WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
5. Commissioning, operation
Pin assignment
Circular connector M12 x 1 (4-pin)
4
3
1
2
U+ 1
U- 3
S+ 2
SP1 4
SP2 2
Legend:
U+ Positive power supply terminal
U- Negative power supply terminal
SP1 Switching output 1
SP2 Switching output 2
S+ Analogue output
16 WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
5.3 Operating modes
System start
Display is fully activated for 2 seconds.
When the ow switch is powered up within the range of the hysteresis, the output switch is set to “not active” by
default.
Display mode
Normal operation, display of ow or temperature value (depending on setting)
Programming mode
Setting the parameters
The in-factory adjustment is carried out with the medium water. It is recommended to carry out the adjustment, relative
to the minimum/maximum ows of the system, via the menu (→ see chapter 5.6 “Adjustment”)
5.4 Keys and functions
The ow switch has two operating modes, the display mode and the programming mode. The selected operating mode
determines the respective function of the key.
Key Function
Jumping into the programming mode
Keep the “MENU” key pressed for approx. 5 seconds. If the password is set to ≠ 0000, a
password will be requested rst.
If authentication is successful, then it enters the programming
mode, otherwise it reverts to display mode.
Returning to the display mode
Simultaneous pressing of both keys.
5. Commissioning, operation
17WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
4-digit LED display
Display ow value
Display of menu item
Display of parameter
Status of switching output 1
Status of switching output 2 (optional)
Display mode
Short press
Display of unit
Long press
Display of the set parameters see chapter 5.5
“Parameters”
Programming mode
Short press
Menu up
Parameter value up (step-wise)
Long press
Menu up
Parameter value up (fast)
Display mode
Short press
Display of unit
Long press
Jumping into the programming mode
Programming mode
Short press
Menu down
Parameter value down (step-wise)
Long press
Menu down
Parameter value down (fast)
Display mode
Short press
Display of unit
Programming mode
Short press
Selection of menu item
Conrmation of input
5. Commissioning, operation
18 WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
5. Commissioning, operation
5.5 Parameter
Parameter Description
SP1/SP2 Hysteresis function: Switch point, switching output (1 or 2)
FH1/FH2 Window function: Window high switching output (1 or 2)
RP1/RP2 Hysteresis function: Reset point, switching output (1 or 2)
FL1/FL2 Window function: Window low switching output (1 or 2)
EF Extended programming functions
RES Reset the set parameters to the factory settings
DS1/DS2 Switch delay time, which must occur without interruption before any electrical signal change occurs (SP1 or SP2)
DR1/DR2 Switch delay time, which must occur without interruption before any electrical signal change occurs (RP1 or RP2)
OU1 / OU2 Switching function switching output (1 or 2)
HNO = hysteresis function, normally open
HNC = hysteresis function, normally closed
FNO = window function, normally open
FNC = window function, normally closed
UNIT Unit switching
SETF Adjustment: Minimum and maximum ow
SETT (option) Measuring range scaling of 4 ... 20 mA temperature output
“Min” determines at which temperature the output signal is to be 4 mA.
“Max” determines at which temperature the output signal is to be 20 mA.
DISM Display value in display mode
FLOW = current ow value; TEMP = current temperature value; OFF = display o;
SP1/FH1 = function switch point 1, RP1/FL1 = function reset point 1,
SP2/FH2 = function switch point 2, RP2/FL2 = function reset point 2
DISR Rotate display by 180°
PAS Password input, 0000 = no password; password input digit by digit
TAG Input of a 16-gure alphanumeric measuring point number
19WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
Display mode
▲ ▼
Long pressing of the “MENU” key
Programming mode
▲ ▼
SP1 / FH1
Value Flow: 5 ... 100 % ; temperature -15 ... +85 °C
▲ ▼
RP1 / FL1
Value Flow: 0 ... 95 % ; temperature -20 ... +80 °C
▲ ▼
SP2 / FH2
Value Flow: 5 ... 100 % ; temperature -15 ... +85 °C
▲ ▼
RP2 / FL2
Value Flow: 0 ... 95 % ; temperature -20 ... +80 °C
▲ ▼
EF
RES
Yes / No Reset to factory settings
▲ ▼
DS1
Value 0 ... 50 s
▲ ▼
DR1
Value 0 ... 50 s
▲ ▼
DS2
Value 0 ... 50 s
▲ ▼
DR2
Value 0 ... 50 s
▲ ▼
OU1
PARA HNO, HNC, FNO, FNC
▲ ▼
OU2
PARA HNO, HNC, FNO, FNC
▲ ▼
UNIT
Unit °C, °F
▲ ▼
SETF
Min Value
Adjustment: Minimum ow
▲ ▼
Max Value
Adjustment: Maximum ow
SETT (option)
Min Value Measuring range scaling: Minimum temperature value
▲ ▼
Max Value Measuring range scaling: Maximum temperature value
DISM
PARA Flow, Temp, SP1, RP1, SP2, RP2, O
▲ ▼
DISR
Yes / No Rotate display by 180°
▲ ▼
PAS
Value Password
▲ ▼
TAG
Value TAG name (16 ASCI characters)
▲ ▼
END END
▼ ▼ ▼ ▼
Display mode
Menu
5. Commissioning, operation
20 WIKA operating instructions flow switch, model FSD-3
EN
14153887.02 08/2017 EN/DE/FR/ES
5. Commissioning, operation
5.6 Adjustment
1. Depressurise the system and switch o the ow.
2
.
Mount the ow switch and connect it electrically.
(→ refer to chapter 5.1 “Mechanical mounting” and 5.2 “Electrical mounting”)
3. Recall menu item “SETF” ▶ “MIN” and conrm “0”.
4. Set the maximum ow in the system.
Observe measuring ranges (→ see chapter 9 “Specications”).
5. Recall menu item “SETF” ▶ “MAX” and conrm “100”.
5.7 Switching functions
Hysteresis function
If the ow rate uctuates around the set point, the hysteresis keeps the
switching status of the outputs stable. With increasing ow rate, the output
switches when reaching the switch point (SP).
Contact normally open (HNO): Active
Contact normally closed (HNC): Inactive
With the ow rate falling again, the output will not switch back before the
reset point (RP) is reached.
Contact normally open (HNO): Inactive
Contact normally closed (HNC): Active
Fig.: Hysteresis function
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132