Installation Guide
Danfoss District Energy VI.IE.A1.5B DKDHR
English - GB
If the household plumbing system includes hot water recirculation the substation must be connected to the hot water recirculation system
by using this circulation set.
It is to be recommended to prepare the substation for recirculation BEFORE mounting it on the wall.
The recirculation pipe in your household plumbing system must be connected to a nipple, mounted on the circulation pipe of the substa-
tion. - See the following pages for information about preparation of substation for and connection to the DHW recirculation system.
Remember always to mount circulation pump, non-return valve on the circulation pipe and to mount safety valve on the DCW inlet.
The pump must be installed so that the pump is pumping water towards the substation.
If a time-controlled pump is used, it is to be recommended that the circulation water temperature is set to approx. 35 °C.
If the circulation pump (outside the substation) is switched o for a longer period, it is to be recommended that the Danfoss bypass ther-
mostat is closed during the same period.
NOTE!
Please note that substations with Danfoss AVE expanion unit must not be used on systems with DHW recirculation.
Circulation set for TDP-F units
Zirkulationsset für TDP-F Stationen
German - DE
Siehe bitte Seiten 13 bis 24.
2
Installation Guide TDP-F units
DKDHR VI.IE.A1.5B Danfoss District Energy
Installation instructions - recirculation connection - Circulation set 1 - 004U8400
You must always t a pump and non-return valve to the recircula-
tion pipe, with ow direction towards the substation.
A safety valve must be mounted in the DCW inlet.
Fig. 1
Remove the nipples/plugs from the domestic hot water controller
(use a 6 mm Allen key).
Fig. 2
Mount hexagon nipple A in the DHW controller (seal with approved
sealing material, - i.e. hemp, tape, glue).
Fig. 3
Fit pipe bushing B in the DHW controller.
Fig. 4
Loosen union nut and demount the existing capillary tube from
the bypass thermostat.
Fig. 5
Lift up the movable section of the insulation cover, as shown, loosen
union nut and demount the existing capillary tube from the angle
piece. Do not re-use the capillary tube.
Fig. 6
Plug the hole with ball C and union nut D.
Fig. 7
Loosen union nut on T-piece for Danfoss bypass thermostat and
turn the angle piece for the capillary tube connection to a 45 de-
gree angle and fasten union nut again.
Fig. 8
Fit new capillary tube E1 by means of cutting rings F and union nuts
D between the bypass thermostat and the pipe bushing B. Tighten
with single end wrench.
Fig. 1 Fig. 2
Fig. 3 Fig. 4
F
A
D
C
G1
B
Akva Lux II TDP-F, Type 004U8264
Fig. 7 Fig. 8
Fig. 5 Fig. 6
G2
H
I
J
K
L
M
E1
E2
33
Installation Guide TDP-F units
Danfoss District Energy VI.IE.A1.5B DKDHR
Fig. 9
Fit circulation hose end G1 in hexagon nipple A (do not forget gas-
ket!), and t the hose through the cut-out in the left side of the rear
insulation cover.
Fig. 10
Mount bracket H for recirculation connection on the mounting rail,
as shown, and fasten by means of two screws I.
Fig. 11
Mount non-return valve J and hexagon nipple K in the pump, as
shown on the photo to your right.
Fig. 12
Loosen union nut.
Fig. 13
Turn pump motor head by 180 degrees. Tighten the union nut
again.
Fig. 14
Please note that the arrow on the back of the housing indicates
the dirction of ow. - Please note the position of the arrow as
shown in the photo to your right.
Fig. 15
Fit pump in bracket H and fasten with locknut L.
Fig. 16
Fit circulation hose end G2 in non-return valve J. (Do not forget
gasket!)
Fig. 17
Akva Lux II TDP-F, prepared for domestic hot water recirculation.
Fig. 9 Fig. 10
Fig. 11
Fig.12
Fig. 13 Fig.14
J
K
Fig. 15 Fig.16
Fig.17
4
Installation Guide TDP-F units
DKDHR VI.IE.A1.5B Danfoss District Energy
You must always t a pump and non-return valve to the recircula-
tion pipe, with ow direction towards the substation.
A safety valve must be mounted in the DCW inlet.
Fig. 1
Remove the nipples/plugs from the domestic hot water controller
(use a 6 mm Allen key).
Fig. 2
Mount hexagon nipple A in the DHW controller (seal with approved
sealing material, - i.e. hemp, tape, glue).
Fig. 3
Fit pipe bushing B in the DHW controller.
Fig. 4
Remove the existing capillary tube and union nut from bypass
thermostat and angle piece (do not re-use).
Fig. 5
Plug the hole in the angle piece with the steel ball C and a union
nut D.
Fig. 6
Fit new capillary tube E2 in bypass thermostat by means of cutting
rings F and a union nut D. Tighten with single end wrench.
Fig. 1 Fig. 2
Akva Lux II TDP-F, Type 004U8089
Akva Lux II TDP-F, Type 004U8044
Cover for wall mounting
Cover for recess mounting
F
A
D
E2
C
G1
B
G2
H
I
J
K
L
M
Fig. 5 Fig. 6
Fig. 3 Fig. 4
E1
55
Installation Guide TDP-F units
Danfoss District Energy VI.IE.A1.5B DKDHR
Fig. 7
Fit/screw hose end G1 onto the hexagon nipple A and t the other
end of the capillary tube E2 in pipe bushing B by means of a cutting
ring F and a union nut D. Tighten with single end wrench.
Fig. 8
Mount bracket H for recirculation connection on the mounting rail,
as shown, and fasten by means of two screws I.
Fig. 9
Mount non-return valve J and hexagon nipple K in the pump, as
shown in the photo to your right.
Fig. 10
Loosen union nut.
Fig. 11
Turn pump motor head by 180 degrees. Tighten the union nut
again.
Fig. 12
Please note that the arrow on the back of the housing indicates
the dirction of ow. - Please note the position of the arrow as
shown in the photo to your right.
Fig. 13
Fit pump in bracket H and fasten with locknut L.
Fig. 14
Fit circulation hose end G2 in non-return valve J. (Do not forget
gasket!)
Fig. 7 Fig. 8
Fig. 9
Fig.10
Fig. 11 Fig.12
J
K
Fig. 13 Fig.14
6
Installation Guide TDP-F units
DKDHR VI.IE.A1.5B Danfoss District Energy
PLEASE NOTE (only for 004U8044):
For systems with DHW recirculation the bypass thermostat
must alway be installed before the heat meter.
On substations, that are supplied with bypass thermo-
stat mounted after the heat meter (Akva Lux II TDP-F, Type
004U8044), the bypass thermostat must therefore be relocated
before the substation is prepared for recirculation, - i.e. the by-
pass thermostat must be mounted before the heat meter.
Please follow the below instructions:
1.
Start by shutting o all connections to the substation.
2.
First follow the instructions for Fig. 1, 2 and 3 on page 16.
3.
Then demount 3/4” plug in T-piece (pos. A), as illustrated in g. 1.
4.
Remove the existing capillary tube from pos. C to D. See g. 2.
5.
Demount bypass thermostat incl. 3/4” reducer bushing from pos. B.
Unscrew 3/4” reducer bushing from bypass thermostat (the 3/4”
reducer bushing is not to be reused). See g. 3.
6.
Mount bypass thermostat in pos A, as illustrated in g. 4.
7.
Plug the hole in pos. B with 3/4” plug (from pos A) and gasket, as
illustrated in g. 5.
8.
Plug the hole in pos. D with a steel ball and 6 mm union nut.
9.
Finally follow instructions for g. 6 to 14 on pages 16 and 17.
Fig. 1
Fig. 2
Fig. 3 Fig. 4
A
B
C
D
Fig. 5
A
D
Fig. 6
B
77
Installation Guide TDP-F units
Danfoss District Energy VI.IE.A1.5B DKDHR
Installation instructions - recirculation connection - Circulation set 2 - 004U8401
You must always t a pump and non-return valve to the recircula-
tion pipe, with ow direction towards the substation.
A safety valve must be mounted in the DCW inlet.
For recirculation connection please refer to installation instructions
for circulation set 1 - 004U8400.
Akva Lux II TDP-F, Type 004U8264
Akva Lux II TDP-F, Type 004U8089
Akva Lux II TDP-F, Type 004U8044
Cover for wall mounting
Cover for recess mounting
F
A
D
C
G1
B
G2
H
I
J
K
L
E2
E1
8
Installation Guide TDP-F units
DKDHR VI.IE.A1.5B Danfoss District Energy
Fig. 1 Fig. 2
Fig. 3
Akva Lux II TDP-F, Type 004U8264
A B
F
H
E
G
D
C
Fig. 4
Fig. 7 Fig. 8
Fig. 5 Fig. 6
Installation instructions - recirculation connection - Circulation set 3 - 004U8403
You must always t a pump and non-return valve to the recircula-
tion pipe, with ow direction towards the substation.
A safety valve must be mounted in the DCW inlet.
Fig. 1
Remove the nipples/plugs from the domestic hot water controller
(use a 6 mm Allen key).
Fig. 2
Mount hexagon nipple A in the DHW controller (seal with approved
sealing material, - i.e. hemp, tape, glue), and mount hexagon nipple
C and union nut D in hexagon nipple A (for tting of recirculation
pipe.
Fig. 3
Fit pipe bushing B in the DHW controller.
Fig. 4
Loosen union nut and demount the existing capillary tube from
the bypass thermostat.
Fig. 5
Lift up the movable section of the insulation cover, as shown, loosen
union nut and demount the existing capillary tube from the angle
piece. Do not re-use the capillary tube.
Fig. 6
Plug the hole with ball E and union nut F.
Fig. 7
Loosen union nut on T-piece for Danfoss bypass thermostat and
turn the angle piece for the capillary tube connection to a 45 de-
gree angle and fasten union nut again.
Fig. 8
Fit new capillary tube G by means of cutting rings H and union nuts
F between the bypass thermostat and the pipe bushing B. Tighten
with single end wrench.
99
Installation Guide TDP-F units
Danfoss District Energy VI.IE.A1.5B DKDHR
You must always t a pump and non-return valve to the recircula-
tion pipe, with ow direction towards the substation.
A safety valve must be mounted in the DCW inlet.
Fig. 1
Remove the nipples/plugs from the domestic hot water controller
(use a 6 mm Allen key).
Fig. 2
Mount hexagon nipple A in the DHW controller seal with approved
sealing material, - i.e. hemp, tape, glue), and mount hexagon nipple
C and union nut D in hexagon nipple A (for tting of recirculation
pipe.
Fig. 3
Fit pipe bushing B in the DHW controller.
Fig. 4
Remove the existing capillary tube and union nut from bypass
thermostat and angle piece (do not re-use).
Fig. 5
Plug the hole in the angle piece with steel ball E and union nut F.
Fig. 6
Fit new capillary tube G in bypass thermostat by means of a cutting
ring H and a union nut F. Tighten with single end wrench.
Fig. 1 Fig. 2
Fig. 3 Fig. 4
Akva Lux II TDP-F, Type 004U8089
Akva Lux II TDP-F, Type 004U8044
Cover for wall mounting
Cover for recess mounting
A B
F
H
E
G
D
C
Fig. 5 Fig. 6
10
Installation Guide TDP-F units
DKDHR VI.IE.A1.5B Danfoss District Energy
Fig. 7
Fit the other capillary tube end G in pipe bushing B by means of a
cutting ring H and a union nut F. Tighten with single end wrench.
PLEASE NOTE (only for 004U8044):
For systems with DHW recirculation the bypass thermostat
must alway be installed before the heat meter.
On substations, that are supplied with bypass thermo-
stat mounted after the heat meter (Akva Lux II TDP-F, Type
004U8044), the bypass thermostat must therefore be relocated
before the substation is prepared for recirculation, - i.e. the by-
pass thermostat must be mounted before the heat meter.
Please follow the below instructions:
1.
Start by shutting o all connections to the substation.
2.
First follow the instructions for Fig. 1, 2 and 3 on page 21.
3.
Then demount 3/4” plug in T-piece (pos. A), as illustrated in g. 1.
4.
Remove the existing capillary tube from pos. C to D. See g. 2.
5.
Demount bypass thermostat incl. 3/4” reducer bushing from pos. B.
Unscrew 3/4” reducer bushing from bypass thermostat (the 3/4”
reducer bushing is not to be reused). See g. 3.
6.
Mount bypass thermostat in pos A, as illustrated in g. 4.
7.
Plug the hole in pos. B with 3/4” plug (from pos A) and gasket, as
illustrated in g. 5.
8.
Plug the hole in pos. D with a steel ball and 6 mm union nut.
9.
Finally follow above instructions for g. 6 and 7 on pages 21 and
22.
Fig. 7
Fig. 1 Fig. 2
Fig. 3 Fig. 4
A
B
C
D
Fig. 5
A
D
Fig. 6
B
1111
Installation Guide TDP-F units
Danfoss District Energy VI.IE.A1.5B DKDHR
Installation instructions - recirculation connection - Circulation set 4 - 004U8405
YYou must always t a pump and non-return valve to the recircu-
lation pipe, with ow direction towards the substation.
A safety valve must be mounted in the DCW inlet.
PLEASE NOTE!
This circulation set can be mounted only on substations without
insulation.
Fig. 1
Remove the nipples/plugs from the domestic hot water controller
(use a 6 mm Allen key).
Fig. 2
Mount hexagon nipple A in the DHW controller (seal with approved
sealing material, - i.e. hemp, tape, glue).
Fig. 3
Mount circulation pipe C, incl. hexagon nipple D, in hexagon nipple
A.
Fig. 4
Fit pipe bushing B in the DHW controller.
Fig. 5
Remove the existing capillary tube and union nut from bypass
thermostat and angle piece (do not re-use).
Fig. 6
Plug the hole in the angle piece with steel ball E and union nut F.
Fig. 1 Fig. 2
Fig. 3 Fig. 4
C
Akva Lux II TDP-F, Type 004U8089
Akva Lux II TDP-F, Type 004U8044
Cover for wall mounting
Cover for recess mounting
A B
F
H
Fig. 5 Fig. 6
E
G
D
12
Installation Guide TDP-F units
DKDHR VI.IE.A1.5B Danfoss District Energy
Fig. 7 Fig. 8
Fig. 7
Fit the new capillary tube G in the bypass thermostat by means of
a cutting ring H and a union nut F. Tighten with single end wrench.
Fig. 8
Fit the other capillary tube end in the pipe bushing by means of a
cutting ring H and a union nut F. Tighten with single end wrench.
PLEASE NOTE (only for 004U8044):
For systems with DHW recirculation the bypass thermostat
must alway be installed before the heat meter.
On substations, that are supplied with bypass thermo-
stat mounted after the heat meter (Akva Lux II TDP-F, Type
004U8044), the bypass thermostat must therefore be relocated
before the substation is prepared for recirculation, - i.e. the by-
pass thermostat must be mounted before the heat meter.
Please follow the below instructions:
1.
Start by shutting o all connections to the substation.
2.
First follow the instructions for Fig. 1, 2, 3 and 4 on page 23.
3.
Then demount 3/4” plug in T-piece (pos. A), as illustrated in g. 1.
4.
Remove the existing capillary tube from pos. C to D. See g. 2.
5.
Demount bypass thermostat incl. 3/4” reducer bushing from pos. B.
Unscrew 3/4” reducer bushing from bypass thermostat (the 3/4”
reducer bushing is not to be reused). See g. 3.
6.
Mount bypass thermostat in pos A, as illustrated in g. 4.
7.
Plug the hole in pos. B with 3/4” plug (from pos A) and gasket, as
illustrated in g. 5.
8.
Plug the hole in pos. D with a steel ball and 6 mm union nut.
9.
Finally follow above instructions for g. 7 and 8 on this page.
Fig. 1 Fig. 2
Fig. 3 Fig. 4
A
B
C
D
Fig. 5
A
D
Fig. 6
B
1313
Installation Guide TDP-F units
Danfoss District Energy VI.IE.A1.5B DKDHR
Div.788 Code No. 004U8400
Div.789 Code No. 004U8401
Div.484 Code No. 004U8403
Div.487 Code No. 004U8405
Zirkulationsset für TDP-F Stationen
German - DE
Wenn eine Zirkulationsleitung in der Hausinstallation vorhanden ist, ist die Station an die Zirkulationsleitung anzuschließen, und eine
Umrüstung von Bypassbetrieb auf TWW-Zirkulation ist mittels dieses Zirkulationssatzes vorzunehmen.
Es wird empfohlen die Station für TWW-Zirkulation VOR der Montage auf der Wand vorzubereiten.
Die Zirkulationsleitung der Hausinstallation ist an einen Messing-Nippel, den auf dem Zirkulationsschlauch der Station montieret ist, an-
zuschliessen. - Siehe die folgende Seiten für weitere Informationen über Zirkulationsanschluss.
Bitte einbau von Umwälzpumpe und Rückschlagventil in der Zirkulationsleitung beachten und Sicherheitsventil in der Kaltwas-
serzuleitung einzubauen. Die Fleißrichtung der Pumpe ist in Richtung Station.
Wird die Umwälzpumpe über eine Schaltuhr gesteuert, empfehlen wir, dass die Zirkulationswassertemperatur auf ungefähr. 35 °C einges-
tellt wird.
Wenn die Umwälzpumpe (außerhalb der Station) für einen längeren Zeitraum abgeschaltet wird, wird es empfohlen, dass der Danfoss
Bypass Thermostat im gleichen Zeitraum geschlossen wird.
BITTE BEMERKEN!
Der AVE Druckausgleichventil ist nicht auf Systemen mit TWW-Zirkulation zu verwenden.
14
Installation Guide TDP-F units
DKDHR VI.IE.A1.5B Danfoss District Energy
Zirkulationsanschluss - Zirkulationsset 1 - 004U8400
Bitte Einbau von Umwälzpumpe und Rückschlagventil in der Zirku-
lationsleitung beachten. Die Fließrichtung der Pumpe ist in Richtung
Station.
Sicherheitsventil in der Kaltwasserzuleitung einbauen.
Abb. 1
Die Nippel/Pfropfe vom Regler abbauen (mit 6 mm Inbusschlüs-
sel).
Abb. 2
Messingnippel A in den Regler einbauen (mit zugelassenem Dicht-
material dichten, - z.B Hanf, Dichtband, Klebsto).
Abb. 3
Nippel B in den Regler einbauen.
Abb. 4
Überwurfmutter lösen und Kapillarrohr von Bypass Thermostat
abbauen.
Abb. 5
Isolierabdeckung heben, Überwurfmutter lösen und Kapillarrohr
vom Winkelstück abbauen (Kapillarrohr verschrotten).
Abb. 6
Mit Kugel C und Überwurfmutter D abdecken.
Abb. 7
Überwurfmutter in T-Stück für Danfoss Bypass Thermostat lösen
und Winkel für Kapillarrohranschluss um ungefähr 45 Grad drehen
und Überwurfmutter wieder festspannen.
Abb. 8
Neues Kapillarrohr E1 mittels Schneidring F und Überwurfmutter D
zwischen Bypass Thermostat und Messingnippel B einbauen. Mit
Schraubenschlüssel festspannen.
Abb. 1 Abb. 2
Abb. 3 Abb. 4
F
A
D
C
G1
B
Akva Lux II TDP-F, Typ 004U8264
Abb. 7 Abb. 8
Abb. 5 Abb. 6
G2
H
I
J
K
L
M
E1
E2
1515
Installation Guide TDP-F units
Danfoss District Energy VI.IE.A1.5B DKDHR
Abb. 9
Zirkulationsschlauchende G1 in Messingnippel A einbauen (Dich-
tung nicht vergessen!), und den Zirkulationsschlauch durch den
Ausschnitt in der linken Seite im Rückisolierung führen.
Abb. 10
Beschlag H für Zirkulationsanschluss auf die Montageplatte, wie
gezeigt, anbringen und mittels die zwei Schrauben I festschrauben.
Abb. 11
Rückschlagventil J und Messingnippel K in die Pumpe wie gezeigt
einbauen.
Abb. 12
Überwurfmutter lösen.
Abb. 13
Pumpenmotorkopf um 180 Grad drehen. Überwurfmutter wieder
anziehen.
Abb. 14
Beachten Sie bitte, dass der Pfeil auf der Rückseite des Gehäuses
die Fließrichtung angibt. - Bitte gezeigte Pfeilrichtung beachten.
Abb. 15
Pumpe in Beschlag H einbauen und mit Sicherungsmutter L
befestigen.
Abb. 16
Zirkulationsschlauchende G2 in Rückschlagventil J einbauen.
(Dichtung nicht vergessen!)
Abb. 17
Akva Lux II TDP-F, vorbereitet für Zirkulationsanschluss.
Abb. 9 Abb. 10
Abb. 11
Abb.12
Abb. 13 Abb.14
J
K
Abb. 15 Abb.16
Abb.17
16
Installation Guide TDP-F units
DKDHR VI.IE.A1.5B Danfoss District Energy
Bitte Einbau von Umwälzpumpe und Rückschlagventil in der Zirku-
lationsleitung beachten. Die Fließrichtung der Pumpe ist in Richtung
Station.
Sicherheitsventil in der Kaltwasserzuleitung einbauen.
Abb. 1
Die Nippel/Pfropfe vom Regler abbauen (mit 6 mm Inbusschlüs-
sel).
Abb. 2
Messingnippel A in den Regler einbauen (mit zugelassenem Dicht-
material dichten, - z.B Hanf, Dichtband, Klebsto).
Abb. 3
Nippel B in den Regler einbauen.
Abb. 4
Kapillarrohr und Überwurfmutter von Bypass Thermostat und
Winkelstück abbauen (verschrotten).
Abb. 5
Mittels Kugel C und Überwurfmutter D in Winkelstück zupfropfen.
Abb. 6
Neues Kapillarrohr E2 in Bypass Thermostat mittels Schneidring
F und Überwurfmutter D in Bypass Thermostat einbauen. - Mit
Schraubenschlüssel festspannen.
Abb. 1 Abb. 2
Akva Lux II TDP-F, Typ 004U8089
Akva Lux II TDP-F, Typ 004U8044
Verkleidung für Aufputzmontage
Verkleidung für Unterputzmontage
F
A
D
E2
C
G1
B
G2
H
I
J
K
L
M
Abb. 5 Abb. 6
Abb. 3 Abb. 4
E1
1717
Installation Guide TDP-F units
Danfoss District Energy VI.IE.A1.5B DKDHR
Abb. 7
Schlauchende G1 an Messingnippel A festschrauben. Das andere
Kapillarrohrende E2 in Messingnippel B mittels Schneidring F und
Überwurfmutter D einbauen. - Mit Schraubenschlüssel festspan-
nen.
Abb. 8
Beschlag H für Zirkulationsanschluss auf die Montageplatte, wie
gezeigt, anbringen und mittels die zwei Schrauben I festschrauben.
Abb. 9
Rückschlagventil J und Messingnippel K in die Pumpe wie gezeigt
einbauen.
Abb. 10
Überwurfmutter lösen.
Abb. 11
Pumpenmotorkopf um 180 Grad drehen. Überwurfmutter wieder
anziehen.
Abb. 12
Beachten Sie bitte, dass der Pfeil auf der Rückseite des Gehäuses
die Fließrichtung angibt. - Bitte gezeigte Pfeilrichtung beachten,
wie in Abb. 12 angegeben.
Abb. 13
Pumpe in Beschlag H einbauen und mit Sicherungsmutter L
befestigen.
Abb. 14
Zirkulationsschlauchende G2 in Rückschlagventil J einbauen.
(Dichtung nicht vergessen!)
Abb. 7 Abb. 8
Abb. 9
Abb.10
Abb. 11 Abb.12
J
K
Abb. 13 Abb.14
18
Installation Guide TDP-F units
DKDHR VI.IE.A1.5B Danfoss District Energy
Beachten Sie bitte (gilt nur für Typ 004U8044):
Auf Anlagen mit Zirkulation ist der Bypass Thermostat immer
vor dem Wärmengenzähler einzubauen.
Auf Stationen, die mit Thermostat nach dem Wärmenmengen-
zähler (Akva Lux II TDP-F, Typ 004U8044) geliefert werden, ist
der Bypass Thermostat deshalb vor Umrüstung af TWW-Zirku-
lation zu verlegen, - d.h. vor dem Wärmemengenzähler ein-
zubauen.
Befolgen Sie bitte die untenstehenden Instruktionen:
1.
Zuerst alle Verbindungen/Anschlüsse zu der Wohnungsstation
abschalten/absperren.
2.
Danach die Instruktionen für Abb. 1, 2 und 3 auf Seite 16 folgen.
3.
Dann 3/4” Pfropfen in T-Stück (Pos. A) abbauen, wie in Abb. 1
abgebildet.
4.
Kapillarrohr von Pos. C zu D abbauen (verschrotten). Siehe Abb. 2.
5.
Bypass-Thermostat einschl. 3/4” Reduzierbusche (Pos. B) abbauen.
Die 3/4” Reduzierbusche von Bypass-Thermostat abbauen (die 3/4”
Reduzierbusche ist nicht wieder zu verwenden). Siehe Abb. 3.
6.
Bypass-Thermostat in Pos A einbauen, wie in Abb. 4 abgebildet.
7.
Das Loch in Pos. B mittels dem 3/4” Pfropfen (von Pos. A) + Dich-
tung zupfropfen, wie in Abb. 5 abgebildet.
8.
Das Loch in Pos. D mittels Kugel und 6 mm Überwurfmutter zu-
pfropfen.
9.
Schließlich den Anweisungen für Abb. 6 bis 14 auf den Seiten 16
und 17 folgen.
Abb. 1
Abb. 2
Abb. 3 Abb. 4
A
B
C
D
Abb. 5
A
D
Abb. 6
B
1919
Installation Guide TDP-F units
Danfoss District Energy VI.IE.A1.5B DKDHR
Zirkulationsanschluss - Zirkulationsset 2 - 004U8401
Bitte Einbau von Umwälzpumpe und Rückschlagventil in der Zirku-
lationsleitung beachten. Die Fließrichtung der Pumpe ist in Richtung
Station.
Sicherheitsventil in der Kaltwasserzuleitung einbauen.
Für Zirkulationsanschluss siehe bitte Anleitung für Zirkulationsset
1 - 004U8400.
Akva Lux II TDP-F, Typ 004U8264
Akva Lux II TDP-F, Typ 004U8089
Akva Lux II TDP-F, Typ 004U8044
Verkleidung für Aufputzmontage
Verkleidung für Unterputzmontage
F
A
D
C
G1
B
G2
H
I
J
K
L
E2
E1
20
Installation Guide TDP-F units
DKDHR VI.IE.A1.5B Danfoss District Energy
Abb. 1 Abb. 2
Abb. 3
Akva Lux II TDP-F, Typ 004U8264
A B
F
H
E
G
D
C
Abb. 4
Abb. 7 Abb. 8
Abb. 5 Abb. 6
Zirkulationsanschluss - Zirkulationsset 3 - 004U8403
Bitte Einbau von Umwälzpumpe und Rückschlagventil in der Zirku-
lationsleitung beachten. Die Fließrichtung der Pumpe ist in Richtung
Station.
Sicherheitsventil in der Kaltwasserzuleitung einbauen.
Abb. 1
Die Nippel/Pfropfe vom Regler abbauen (mit 6 mm Inbusschlüs-
sel).
Abb. 2
Messingnippel A in den Regler einbauen (mit zugelassenem Dicht-
material dichten, - z.B Hanf, Dichtband, Klebsto) und Messingnip-
pel C und Überwurfmutter D in Messingnippel A einbauen. (Für
Einbau eines Zirkulationsrohres).
Abb. 3
Nippel B in den Regler einbauen.
Abb. 4
Überwurfmutter lösen und Kapillarrohr von Bypass Thermostat
abbauen.
Abb. 5
Isolierabdeckung heben, Überwurfmutter lösen und Kapillarrohr
vom Winkelstück abbauen (Kapillarrohr verschrotten).
Abb. 6
Mit Kugel E und Überwurfmutter F abdecken.
Abb. 7
Überwurfmutter in T-Stück für Danfoss Bypass Thermostat lösen
und Winkel für Kapillarrohranschluss um ungefähr 45 Grad drehen
und Überwurfmutter wieder festspannen.
Abb. 8
Neues Kapillarrohr G mittels Schneidring H und Überwurfmutter F
zwischen Bypass Thermostat und Messingnippel B einbauen. Mit
Schraubenschlüssel festspannen.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Danfoss 144B2006 Installationsanleitung

Typ
Installationsanleitung
Dieses Handbuch eignet sich auch für

in anderen Sprachen