UC4
Ultrasonic sensor – Operating instructions
Safety notes
•
Read the operating instructions before commissioning.
•
Connection, mounting, and conguration may only be
performed by trained specialists.
•
When commissioning, protect the device from moisture
and contamination.
•
Not a safety component in accordance with the EU
Machinery Directive.
Intended use
UC4 sensors are ultrasonic sensors for non-contact detec-
tion of objects, animals, and persons.
Notes
•
To ensure the teach-in button functions correctly, press
the teach-in button in the center at a right angle.
•
Distance measurement is not possible below the opera-
ting range of the UC4 ultrasonic sensor.
•
During operation with the lter setting F00 (can be set via
SOPAS and IO-Link), EMC interference can cause system-
inherent subsequent disruption times of up to one output
time. After this the sensor returns to full working order.
•
During normal operation, an orange LED lights up to sig-
nal that the switching output is active (for sensors with a
switching output) or that an object is in the scaling area
(for sensors with an analog output).
•
Some UC4 sensors have an internal temperature com-
pensation function. Due to the sensor heating up, the
temperature compensation function will reach its optimal
working point after approximately one minute.
Temperature compensation is calibrated for standard
mounting conditions, using an aluminum mounting bracket
and mounting screws, at the factory. It is automatically
and optimally calibrated to the individual installation
situation when the sensor is cold and the switching out-
put has been deactivated for approx. 30 minutes, or the
analog output has been outputting a constant value of
between 11 and 13 mA or 4.4. and 5.6 V for approx.
30 minutes. If the measured value changes over the
course of these 30 minutes, the calibration process run-
ning in the background is aborted. The standard para-
meters or the parameters last calibrated are retained.
This function is very helpful when the installation situati-
on diers greatly from the standard mounting conditions
(e.g., in the case of thermally insulated mounting) and
a very high level of accuracy is required.
•
The UC4-1334A and UC4-13x4B sensors are IO-Link-
capable in accordance with the V1.1 specication. A
description of IO-Link functions and the latest IODD for
these sensors are available at www.sick.com/UC4.
Mounting distances
If you want to operate several ultrasonic sensors, you must
comply with the following mounting distances.
Parallel Opposite
UC4 > 250 mm > 1,300 mm
Commissioning
For instructions, see:
•
Process diagram D for sensors with switching outputs
•
Process diagram E for sensors with analog outputs
Sensors with switching outputs
There are three operating modes for sensors with switching
outputs.
•
Teach in switching point (+8%):
The switching output is active when the object is located
either below the taught-in switching point or below the
taught-in switching point +8%.
•
Teach in switching window:
The switching output is active when the object is located
inside the taught-in window.
•
Teach in background:
The switching output is inactive when the object is located
either below the taught-in reector -8% or above the
taught-in reector +8%.
Sensors with analog outputs
See process diagram E.
•
Teach in scaling (4 mA ... 20 mA or 0 V ... 10 V):
If the distant sensor scaling limit is taught-in rst, followed
by the close sensor scaling limit, then the scaling limits
are replaced internally.
If scaling less than 1 mm or less than the minimum oper-
ating range is taught in, then both LEDs ash rapidly to-
gether for 3 seconds as an error indication. The old scaling
limits are retained.
Further settings for all sensors
•
Deactivate/Activate teach-in button
•
Reset to factory settings.
See process diagram D for sensors with switching outputs.
See process diagram E for sensors with analog outputs.
Maintenance
SICK sensors are maintenance-free. We do, however, recom-
mend that the following activities are undertaken regularly:
– Clean the external surfaces carefully with water
– Check screw connections and plug connectors.
C
0
40
(1.57)
280
200
(7.87)
240
(9.45)
120
(4.72)
160
(6.30)
80
(3.15)
80
(3.15)
120
(4.72)
120
(4.72)
80
(3.15)
40
(1.57)
40
(1.57)
0
Detection area in mm (inch)
Detection area in mm (inch)
5
3
2
4
1
0
40
80
120
160
(6.30)
Detection area in mm (inch)
40
(1.57)
60
(2.36)
60
(2.36)
40
(1.57)
20
(0.79)
20
(0.79)
0
Detection area in mm (inch)
5
3
2
4
1
UC4-11xxx
Detection area
1 Detection area depending on reexion properties,
size and alignment of the object
2 Limiting range
3 Operating range
4 Example object: Aligned plate 100 mm x 100 mm
5 Example object: Pipe with diameter 10 mm
UC4-13xxx
1 Threaded mounting hole M3
2 Connection
3 LED status indicator switching output/
analog output (orange)
4 LED status indicator supply voltage active (green)
5 Teach-in button
6 Variant with 300 mm connecting cable and M8 male
connector, 3-pin
F
Technical data
B
Electrical connection
EN UC4-11341 UC4-11345 UC4-13341 UC4-13345 UC4-13341S01 UC4-13345S02 UC4-1334A/UC4-1334B UC4-1354B UC4-13346 UC4-13347
Operating range
1)
13 mm … 100 mm 13 mm … 150 mm 13 mm … 150 mm 13 mm … 150 mm 20 … 150 mm
Limiting range 150 mm 250 mm 250 mm 250 mm 250 mm
Ultrasonic frequency (typical) 380 kHz 380 kHz 380 kHz 380 kHz 380 kHz
Hysteresis 2 mm 2 mm 2 mm 2 mm –
Resolution ≥ 0.1 mm ≥ 0.1 mm ≥ 0.1 mm ≥ 0.1 mm ≥ 0.1 mm
Reproducibility ± 0.15% in relation to the current measured value ± 0.15% in relation to the current measured value ± 0.15% in relation to the current measured value ± 0.15% in relation to the current measured value ± 0.15% in relation to the current measured value
Accuracy ≤ 0.17% / K ± 1% in relation to the current measured value ≤ 0.17% / K ± 1% in relation to the current measured value ± 1% in relation to the current measured value
Supply voltage U
V
2)
DC 15 ... 30 V DC 15 ... 30 V DC 15 ... 30 V DC 15 ... 30 V DC 15 ... 30 V
Power consumption (without load) ≤ 0.75 W ≤ 0.75 W ≤ 0.9 W ≤ 0.75 W ≤ 0.75 W
Housing material ABS plastic; ultrasonic converter: polyurethane foam, epoxy resin with glass content
Enclosure rating as per EN 60529 IP 67 IP 67 IP 67 IP 67 IP 67
Protection class III III III III III
Connection type Male connector, M8, 3-pin Male connector, M8, 3-pin Male connector, M8, 3-pin Male connector, M8, 3-pin Connecting cable (approx.
100 mm, PVC), male
connector, M8, 3-pin
Male connector, M8, 3-pin
Ambient temperature
3)
Operation: –25 °C ... +70 °C, warehouse: –40 °C ... +85 °C
Weight 10 g 10 g 10 g 10 g 10 g
Analog output not available not available not available not available 4 mA … 20 mA: RL ≤ 500 Ω 0 V … 10 V: RL ≥ 100 kΩ
Switching output 1 x PNP (200 mA)
4), 5),
1 x NPN (200 mA)
4), 5),
1 x PNP (200 mA)
4), 5)
1 x NPN (200 mA)
4), 5)
1 x PNP (200 mA)
4), 5)
1 x NPN (200 mA)
4), 5)
Push-pull: PNP/NPN (100 mA); IO-Link V1.1
4), 6), 7)
not available
Output time 8 ms 8 ms 5 ms 8 ms 8 ms
Switching frequency 30 Hz 30 Hz 100 Hz 30 Hz –
Response time 24 ms 24 ms 10 ms 24 ms 24 ms
8)
Initialization time < 300 ms < 300 ms < 300 ms < 300 ms < 300 ms
Temperature compensation No Yes No Yes Yes
1)
Teach-in from 21 mm
2)
Limit values, reverse polarity protected. Operation in short-circuit protected network max. 8 A
3)
At operating temperatures of > 50 °C, the rear side of the UC4 must be installed with its surface at against a bracket.
4)
Output Q short-circuit protected
5)
PNP: HIGH = U
V
– (2 V); LOW = 0 V/NPN: HIGH ≤ 2 V; LOW = U
V
6)
Push-pull PNP/NPN: HIGH = U
V
– (< 3 V); LOW = < 3 V
7)
UC4-1334B: “Enhanced function classes according to the IO-Link 1.1 specication”
8)
Subsequent smoothing of the analog output may increase the response time by up to 200% in some applications.
D
Sensors with switching output
Teach-in switching output and further settings
1
Teach-in switching point
IO-Link: Single point (DtO)
Position object at 1
Press teach-in button
for approx. 2 s,
until the orange LED flashes.
flash alternatelyBoth LEDs:
Teach-in switching window
IO-Link: Window (window mode)
21
Press teach-in button
for approx. 5 s,
until the green LED flashes.
Position object at 1
Press teach-in button
for approx. 1 s.
Position object at 2
Teach-in background
IO-Link: Window ± 8 % (ObSB)
Press teach-in button
for approx. 5 s,
until the green LED flashes.
flash alternatelyBoth LEDs:
Press teach-in button
for approx. 10 s,
until the green LED is on.
Position background at 1
Set normally closed /
normally open contact
Wait approx. 10 s.
Press teach-in button
for approx. 13 s, until
both LEDs flash alternately.
flashes: normally openOrange LED:
Green LED: flashes: normally closed
To change the setting
press the teach-in button
for approx. 1 s.
Position object
in the detection area.
Reset to
the factory setting
Switch off the
supply voltage.
With teach-in button
pressed down, switch on
the supply voltage and
keep pressed for approx. 13 s,
until the green LED is on.
Deactivate / Activate
teach-in button
Switch off the
supply voltage.
With teach-in button pressed down,
switch on the supply voltage
and keep pressed for approx. 5 s,
until the orange LED flashes.
flashes: button activatedOrange LED:
Green LED: flashes: button deactivated
Wait approx. 10 s.
To change the setting
press the teach-in button
for approx. 1 s.
Status changes.
Normal operation
Status changes.
Default setting: Normally open contact, switching point (DtO) at max. operating range
1
– 8 %
+ 8 %
E
Sensors with analog output
Press teach-in button
for approx. 1 s.
Position object at 2
12
Teach-in analog output and further settings
flash alternatelyBoth LEDs:
Wait approx. 10 s.
Press teach-in button
for approx. 13 s, until
both LEDs flash alternately.
flashesGreen LED:
Orange LED: on: rising output characteristics
off: falling output characteristics
To change the output
characteristics press the
teach-in button for approx. 1 s.
Orange LED:
changes status
Reset to
the factory setting
Switch off the
supply voltage.
Deactivate / Activate
teach-in button
Switch off the
supply voltage.
With teach-in button pressed down,
switch on the supply voltage
and keep pressed for approx.
3 s, until the orange LED flashes.
flashesGreen LED:
Orange LED: flashes: button activated
flashes not: button deactivated
Wait approx. 10 s.
To change the setting
press the teach-in button
for approx. 1 s.
Normal operation
Press teach-in button
for approx. 3 s, until
both LEDs flash simultaneously.
Position object at 1
Teach-in
analog output scaling
Setting rising / falling
output characteristics
Orange LED:
changes status
With teach-in button
pressed down, switch on the
supply voltage and keep pressed
for approx. 13 s, until both
LEDs flash simultaneously.
Default setting: Rising output characteristics from min. to max. operating range
Male connector, M8, 3-pin
1
UC4-11341
UC4-11345
UC4-13341
UC4-13345
(UC4-13341S01)
(UC4-13345S02)
UC4-1334A
UC4-1334B
UC4-1354B
UC4-13346
UC4-13347
L+
M
1
3
4
brn
blu
q/
blk
L+
M
1
3
4
brn
blu
q/Q
blk
L+
M
1
3
4
brn
blu
q
blk
www.sick.com/uc4
BZ int48
Please find detailed addresses and further locations in all major industrial
nations at www.sick.com
Australia
Phone +61 (3) 9457 0600
Austria
Phone +43 (0) 2236 62288-0
Belgium/Luxembourg
Phone +32 (0) 2 466 55 66
Brazil
Phone +55 11 3215-4900
Canada
Phone +1 905.771.1444
Czech Republic
Phone +420 2 57 91 18 50
Chile
Phone +56 (2) 2274 7430
China
Phone +86 20 2882 3600
Denmark
Phone +45 45 82 64 00
Finland
Phone +358-9-25 15 800
France
Phone +33 1 64 62 35 00
Germany
Phone +49 (0) 2 11 53 01
Hong Kong
Phone +852 2153 6300
Hungary
Phone +36 1 371 2680
India
Phone +91-22-6119 8900
Israel
Phone +972-4-6881000
Italy
Phone +39 02 27 43 41
Japan
Phone +81 3 5309 2112
Malaysia
Phone +603-8080 7425
Mexico
Phone +52 (472) 748 9451
Netherlands
Phone +31 (0) 30 229 25 44
New Zealand
Phone +64 9 415 0459
Norway
Phone +47 67 81 50 00
Poland
Phone +48 22 539 41 00
Romania
Phone +40 356-17 11 20
Russia
Phone +7 495 283 09 90
Singapore
Phone +65 6744 3732
Slovakia
Phone +421 482 901 201
Slovenia
Phone +386 591 78849
South Africa
Phone +27 (0)11 472 3733
South Korea
Phone +82 2 786 6321
Spain
Phone +34 93 480 31 00
Sweden
Phone +46 10 110 10 00
Switzerland
Phone +41 41 619 29 39
Taiwan
Phone +886-2-2375-6288
Thailand
Phone +66 2 645 0009
Turkey
Phone +90 (216) 528 50 00
United Arab Emirates
Phone +971 (0) 4 88 65 878
United Kingdom
Phone +44 (0)17278 31121
USA
Phone +1 800.325.7425
Vietnam
Phone +65 6744 3732