IFM OB5014 Installationsanleitung

Typ
Installationsanleitung

Dieses Handbuch ist auch geeignet für

Bedienungsanleitung
Operating instructions
Notice pour utilisateurs
Schaltverstärker für
Fiberoptik OBF
Switching amplifier for
fibre optics OBF
Amplificateur pour
fibre optique OBF
R
Sachnr. 701059 / 03 08 / 03
Deutsch
Bestimmungsgemäße Verwendung D1
Bedien- und Anzeigeelemente D1
Montage D2
Adaptieren der Lichtleiter D2
Elektrischer Anschluß D2
Schaltschwelle automatisch einstellen (1) D3
Schaltschwelle automatisch einstellen (2) D4
Schaltschwelle manuell einstellen (1) D5
Schaltschwelle manuell einstellen (2) D6
Einstellen der Impulsverlängerung D7
Betrieb D7
English
Intended use E1
Controls and indicators E1
Mounting E2
Mount the fibre optics E2
Electrical connection E2
Automatic setting of the switching threshold (1) E3
Automatic setting of the switching threshold (2) E4
Manual setting of the switching threshold (1) E5
Manual setting of the switching threshold (2) E6
Adjust of the pulse stretching E7
Operation E7
Français
Fonctionnement et caractéristiques F1
Eléments de service et d’indication F1
Montage F2
Monter les fibres optiques F2
Raccordement électrique F2
Réglage automatique du seuil de commutation (1) F3
Réglage automatique du seuil de commutation (2) F4
Réglage manuel du seuil de commutation (1) F5
Réglage manuel du seuil de commutation (2) F6
Régler la prolongation d’impulsion F7
Fonctionnement F7
2
Bestimmungsgemäße Verwendung
Der Schaltverstärker erfaßt berührungslos Gegenstände und Materialien
und meldet sie durch ein Schaltsignal.
Nur für den Anschluß der ifm-Fiberoptiken Typ FE-11 und FT-11.
Reich- und Tastweite je nach Fiberoptik.
Impulsverlängerung, 0 oder 2 ... 90 ms einstellbar.
(Jeder Eingangsimpuls wird auf den eingestellten Wert verlängert).
Bedien- und Anzeigeelemente
3
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
Grüne LEDs:
- im Betriebsmodus: Betriebsreserve in %
- im Programmiermodus: Stärke des Eingangssignals
Rote LED:
leuchtet im unsicheren Empfangsbereich (Dejustage,
Verschmutzung der Optik)
T2: Start der Einstellung für die Impulsverlängerung
Gelbe LED:
leuchtet, wenn der Ausgang durchgeschaltet ist
Grüne LED:
leuchtet bei Betriebsbereitschaft
T1: Start der automatischen Schaltschwellen-
einstellung
T1 + T2: Start der manuellen Schaltschwellen-
einstellung
D1
Montage
Befestigen Sie das Gerät auf einer Normschiene oder mit Hilfe einer
Montagehalterung.
Adaptieren der Lichtleiter:
1. Lösen Sie die Schraube A (Abb. 1).
2. Schieben Sie die Lichtleiter in die Sensoröffnungen B, bis Sie einen
leichten Widerstand spüren (O-Ring) (Abb. 2).
3. Schieben Sie die Lichtleiter weiter bis zum Anschlag (Optik-Elemente)
und halten Sie sie fest (Abb. 3).
4. Ziehen Sie die Schraube A an.
Liegen die Lichtleiter nicht an den Optik-Elementen an, veringert
sich die Reich- / Tastweite.
Elektrischer Anschluß
Schalten Sie die Anlage spannungsfrei und schließen Sie das
Gerät an (s. letzte Seite oder Typaufkleber).
Adernfarben bei Kabelgeräten: BN = braun, BU = blau, BK = schwarz,
VT = violett.
Programmieren der Ausgangsfunktion durch Anschlußbelegung
(s. letzte Seite oder Typaufkleber).
Belastung des Funktionskontroll-Ausgangs (fc-output): max. 10mA.
4
A
B
12 3
D2
5
Schaltschwelle automatisch einstellen (1)
Objekte bewegen sich durch den Erfassungsbereich der Optik
Lichttaster-Optik (FT ...) und Einweg-Optik (FE ...)
Das Gerät erfaßt Eingangssignale verschiedener Intensität in beliebiger
Reihenfolge und berechnet die optimale Schaltschwelle.
Ist die Einstellung der Schaltschwelle nicht möglich (z. B. Hellsignal
und Dunkelsignal sind annähernd gleich stark), blinkt die LED-
Kette nach Schritt 3. Danach geht das Gerät mit unveränderter
Schaltschwelle in den Betriebsmodus über.
out
on
out
on out
on
out
on
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
1
3
2
Lassen Sie die Objekte durch den
Erfassungsbereich der Optik laufen.
Drücken Sie, bis LED-Kette blinkt.
Drücken Sie 1 mal.
Drücken Sie 1 mal.
LEDs gelb und grün
blinken im Wechsel
(= Gerät ist im
Programmiermodus).
LEDs gelb und grün
verlöschen kurzzeitig,
blinken dann wieder
im Wechsel.
LEDs gelb und grün
verlöschen kurzzeitig,
danach leuchtet die
grüne LED
(= das Gerät ist im
Betriebszustand).
D3
Schaltschwelle automatisch einstellen (2)
Statische Objekte
Lichttaster-Optik (FT ...) und Einweg-Optik (FE ...)
Das Gerät erfaßt Eingangssignale verschiedener Intensität in beliebiger
Reihenfolge und berechnet die optimale Schaltschwelle.
*Sie können auch in umgekehrter Reihenfolge vorgehen: Zuerst ohne Objekt
messen, dann mit Objekt.
Ist die Einstellung der Schaltschwelle nicht möglich (z. B. Hellsignal
und Dunkelsignal sind annähernd gleich stark), blinkt die LED-
Kette nach Schritt 3. Danach geht das Gerät mit unveränderter
Schaltschwelle in den Betriebsmodus über.
6
out
on
out
on out
on
out
on
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
1
3
2
Plazieren Sie das Objekt im
Erfassungsbereich der Optik.*
Entfernen Sie das Objekt aus dem
Erfassungsbereich der Optik.*
Drücken Sie, bis LED-Kette blinkt.
Drücken Sie 1 mal.
Drücken Sie 1 mal.
LEDs gelb und grün
blinken im Wechsel
(= Gerät ist im
Programmiermodus).
LEDs gelb und grün
verlöschen kurzzeitig,
blinken dann wieder
im Wechsel.
LEDs gelb und grün
verlöschen kurzzeitig,
danach leuchtet die
grüne LED
(= das Gerät ist im
Betriebszustand).
D4
Schaltschwelle manuell einstellen (1)
Statische Objekte / Lichttaster-Optik (FT ...)
7
out
on
out
on
90
70
50
30
10
ms
400
200
150
100
50
%
90
70
50
30
10
ms
400
200
150
100
50
%
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
1
Drücken Sie, bis LED-Kette blinkt.
LED grün blinkt,
LED gelb zeigt
Schaltzustand
(= Gerät ist im
Programmiermodus).
2Plazieren Sie das Objekt im
Erfassungsbereich der Optik. Objektsignal wird gemessen und
angezeigt (= Kette der schwach
leuchtenden LEDs);
hell blinkende LED = aktuelle
Schaltschwelle.
5
Drücken Sie, bis LED-Kette blinkt.
LED grün leuchtet
(= Gerät ist im
Betriebszustand).
4Drücken Sie die Tasten + oder
-, bis die Schaltschwelle in der
Mitte zwischen Hintergrundsignal
und Objektsignal liegt;
(hier Schaltschwelle verringern).
3Entfernen Sie das Objekt aus
dem Erfassungsbereich der Optik. Hintergrundsignal wird gemessen
und angezeigt (= Kette der
schwach leuchtenden LEDs).
D5
Schaltschwelle manuell einstellen (2)
Statische Objekte / Einweg-Optik (FE ...)
8
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
out
on
out
on
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
Drücken Sie, bis LED-Kette blinkt.
LED grün blinkt
LED gelb zeigt
Schaltzustand
(= Gerät ist im
Programmiermodus).
2Drücken Sie die Taste -, bis die
LED-Kette die niedrigste Schalt-
schwelle anzeigt.
3
Plazieren Sie das Objekt im
Erfassungsbereich der Optik.
Drücken Sie die Taste +, bis das
Gerät schaltet (LED gelb leuchtet
auf oder verlischt).
oder
4Drücken Sie, bis LED-Kette blinkt.
LED grün leuchtet
(= das Gerät ist im
Betriebszustand).
D6
1
Einstellen der Impulsverlängerung
Betrieb
Öffnen Sie den Gehäusedeckel nur zum Einstellen. Schließen Sie ihn
nach der Einstellung, um Schutzart IP 65 zu erhalten.
Prüfen Sie, ob das Gerät sicher funktioniert. Anzeige durch LEDs und
durch Funktionskontroll-Ausgang:
Rote LED leuchtet: Störung bei der Objekterfassung (mangelhafte
Objekterkennung; Dejustage; Verschmutzung der Optik).
LED-Kette blinkt schnell bei Kurzschluß des Schaltausgangs, lang-
sam bei interner Störung.
Der Funktionskontroll-Ausgang ist geschaltet bei:
Störung der Objekterfassung (mangelhafte Objekterkennung; Deju-
stierung, Verschmutzung der Optik); automatisch zurückgesetzt,
wenn die Störung beseitigt ist.
Kurzschluß des Schaltausgangs; automatisch zurückgesetzt ca. 4 sec
nach Beseitigung der Störung.
9
90
70
50
30
10
ms
out
on
out
on
0
2 - 10
11 - 20
21 - 30
31 - 40
41 - 50
51 - 60
61 - 70
71 - 80
81 - 90
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
1
Drücken Sie, bis LED-Kette blinkt.
LEDs gelb und grün
blinken im Wechsel
(= Gerät ist im
Programmiermodus).
2
Drücken Sie die Taste + oder
-, um die gewünschte
Verzögerungszeit einzustellen
(hier: Verzögerungszeit erhöhen).
Tastendruck entspricht ca. 1ms;
Schnellauf: Taste gedrückt halten.
Zeit(ms) leuchtende LEDs
3Warten Sie ca. 10s lang. LED grün leuchtet
(=Gerät ist im
Betriebszustand).
D7
Intended use
The switching amplifier senses objects and materials without contact
and indicates their presence by a switching signal.
Only for the connection of the ifm fibre optics type FE-11 and FT-11.
Sensing range depends on the fibre optic.
Pulse stretching 0 or adjustable between 2 and 90ms.
(Each input pulse is stretched to the set value).
Controls and indicators
10
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
green LEDs:
- in operating mode: excess gain in %
- in programming mode: strength of input signal
red LED:
lights in the uncertain reception zone
(maladjustment, soiling of the lens)
T2: starts the setting of the pulse stretching
yellow LED:
switching status, lights when the output is
switched
green LED:
lights when ready for operation
T1: starts the automatic setting of the switching
threshold
T1 + T2: starts the manual setting of the
switching threshold
E1
11
Mounting
Mount the unit on a DIN rail or by means of a mounting fixture.
Mount the fibre optics:
1. Loosen the screw A, fig. 1.
2. Place the fibre optics into the sensor holes B until you feel a sligh
resistance (O ring), fig. 2.
3. Push the fibre optics until they come to a stop (optical elements) and
hold them, fig. 3.
4.Tighten the screw A.
If the fibre optics are not in contact with the optical elements,
the sensing range is reduced.
Electrical connection
Isolate the power, then connect the unit as specified (see the last
page or the type label).
Core colours (for sensors with cable connection): BN = brown,
BU = blue, BK = black, VT = violet.
Programming of the output function by wiring (see the last page or
the type label).
Load of the function check output (fc-output): max. 10mA.
A
B
12 3
E2
Automatic setting of the switching threshold (1)
Objects move through the detection area
Diffuse reflection fibre (FT ...) and through-beam fibre (FE ...)
The unit detects input signals of various intensity in any sequence and
calculates the optimum switching threshold.
If the setting of the switching threshold is not possible (e.g.
object signal and background signal are about the same), the
row of LEDs flashes after step 3. The unit then passes into the
operating mode with the switching threshold being unchanged.
12
out
on
out
on out
on
out
on
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
1
3
2
Allow the objects to pass trough
the detection area.
Press until the row of LEDs flashes.
Press once.
Press once.
Yellow and green LEDs
flash alternately
(= unit is in the
programming mode).
Yellow and green
LEDs go out for a short
time, then flash again
alternately.
Yellow and green
LEDs go out for a
short time,
then the green LED is on
(= unit is in the
operating mode).
E3
Automatic setting of the switching threshold (2)
Stationary objects
Diffuse reflection fibre (FT ...) and through-beam fibre (FE ...)
The unit detects input signals of various intensity in any sequence and
calculates the optimum switching threshold.
* You can also proceed in reverse order: first setting without the object, then
with the object.
If the setting of the switching threshold is not possible (e.g.
object signal and background signal are about the same), the
row of LEDs flashes after step 3. The unit then passes into the
operating mode with the switching threshold being unchanged.
13
out
on
out
on out
on
out
on
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
1
3
2
Place the object into the
detection area.*
Press until the row of LEDs flashes.
Press once.
Press once.
Yellow and green LEDs
flash alternately
(= unit is in the
programming mode).
Yellow and green
LEDs go out for a short
time, then flash again
alternately.
Yellow and green
LEDs go out for a
short time,
then the green LED is on
(= unit is in the
operating mode).
E4
Remove the object.*
Manual setting of the switching threshold (1)
Stationary objects / Diffuse reflection fibre (FT ...)
14
out
on
out
on
90
70
50
30
10
ms
400
200
150
100
50
%
90
70
50
30
10
ms
400
200
150
100
50
%
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
1
Press until the row of LEDs flashes.
Green LED flashes,
yellow LED indicates the
switching status
(= unit is in the
programming mode).
2Place the object into the
detection area. Object signal is measured and
indicated (= row of dimly lit LEDs)
brightly flashing LED = current
switching threshold.
5
Press until the row of LEDs flashes.
Green LED lights
(= unit is in the
operating mode).
4Press the + or - button until
the switching threshold is in the
middle between the background
signal and the object signal;
(here: reducing the switching
threshold).
3Remove the object.
Background signal is measured
and indicated
(= row of dimly lit LEDs).
E5
Manual setting of the switching threshold (2)
Stationary objects / through-beam fibre (FE ...)
15
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
out
on
out
on
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
1
Press until the row of LEDs flashes.
Green LED flashes,
yellow LED indicates the
switching status
(= unit is in the
programming mode).
2Press the - button until the
row of LEDs indicates the
lowest switching threshold.
3
Place the object into the
detection area.
Press the + button until the
unit switches (yellow LED lights
or goes out).
or
4Press until the row of LEDs flashes.
Green LED lights
(= unit is in the
operating mode).
E6
Adjust of the pulse stretching
Operation
Only open the cover to make adjustments. Close it after the adjust-
ment has been made in order to maintain the protection IP65.
Check whether the unit functions properly. Indication by LEDs and by
the function check output:
Red LED lights: wrong sensing of the object (maladjustment, soiling
of the lens).
Row of LEDs flashes qickly: output short-circuited / slowly: internal
malfunction.
The function check output switches in the case of
wrong sensing of the object (maladjustment, soiling of the lens),
reset after the object has been sensed again properly;
a short circuit of the switching output, reset about 4s after the fault
has been eliminated.
16
90
70
50
30
10
ms
out
on
out
on
0
2 - 10
11 - 20
21 - 30
31 - 40
41 - 50
51 - 60
61 - 70
71 - 80
81 - 90
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
1
Press until the row of LEDs flashes.
Yellow and green LEDs
flash alternately
(= unit is in the
programming mode).
2
Press the + or - button to set
the desired delay time
(here: increasing delay time).
1 x = about 1ms;
hold the button pressed for fast
setting.
time (ms) lit LEDs
3Wait for approx. 10s. Green LED lights
(= unit is in the
operating mode).
E7
Fonctionnement et caractéristiques
Lamplificateur détecte des objets et des matières sans contact et
indique leur présence par un signal de commutation.
Pour raccordement aux fibres optiques ifm forme FE-11 et FT-11
seulement.
Portée selon la fibre optique.
Prolongation dimpulsion, 0 ou réglable entre 2 et 90ms.
(Chaque impulsion dentrée est prolongée à la valeur réglée).
Eléments de service et dindication
17
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
LED vertes:
- en mode fontionnement: capacité de réserve en %
- en mode programmation: intensité du signal dentrée
LED rouge:
allumée dans la zone de réception non sûre
(mauvais réglage; encrassement des fibres)
T2: démarrage du réglage de la prolongation
dimpulsion
LED jaune:
état de commutation; allumée si lappareil est
commuté
LED verte:
allumée si lamplificateur est disponible
T1: démarrage du réglage automatique du seuil
de commutation
T1+T2: démarrage du réglage manuel du seuil de
commutation
F1
Montage
Monter lappareil sur un profilé normalisé (rail DIN) ou à laide dun dis-
positif de montage.
Monter les fibres optiques comme suit:
1. Dévisser la vis A (fig. 1).
2. Glisser les fibres optiques dans les ouvertures de lamplificateur B
jusqu’à ce quon remarque une faible résistance (joint torique)
(fig. 2).
3. Avancer les fibres optiques jusqu’à larrêt (éléments optiques) et les
retenir (fig. 3).
4.Serrer la vis A.
Si les fibres optiques ne sont pas en contact direct avec les élé-
ments optiques, la portée sera réduite.
Raccordement électrique
Mettre linstallation hors tension avant le raccordement. Raccor-
dement selon les indications de la dernière page ou selon
l’étiquette.
Couleurs des fils (pour les cellules avec raccordement par câble):
BN = brun, BU = bleu, BK = noir, VT = violet.
Programmation de la fonction de sortie par branchement selon les
indications de la dernière page ou selon l’étiquette.
Charge de la sortie diagnostique (fc-output): 10mA maxi.
18
A
B
12 3
F2
Réglage automatique du seuil de commutation (1)
Des objets passent à travers le faisceau optique
Fibre optique réflexion directe (FT ...) et fibre optique barrage (FE ...)
La cellule détecte les signaux dentrée de différente intensité dans
nimporte quelle ordre et calcule le seuil de commutation optimale.
Si le réglage du seuil de commutation nest pas possible (p. ex.
le signal de lobjet et le signal de larrière-plan ont presque la
même intensité), la rampe de LED clignote après l’étage de réglage
no. 3. Ensuite la cellule passe au mode fonctionnement sans
changer le seuil de commutation.
19
out
on
out
on out
on
out
on
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
1
3
2
Faire passer les objets à travers le
faiscau optique.
Appuyer jusqu’à ce
que la rampe de LED clignote.
Appuyer une fois.
Appuyer une fois.
Les LED jaune et verte
clignotent
alternativement
(= la cellule est en mode
programmation).
Les LED jaune et verte
s’éteignent brièvement,
ensuite elles clignotent
de nouveau
alternativement.
Les LED jaune et verte
s’éteignent brièvement,
ensuite la LED verte
sallume
(= la cellule est en
mode fonctionnement).
F3
Réglage automatique du seuil de commutation (2)
Objets immobiles
Fibre optique réflexion directe (FT ...) et fibre optique barrage (FE ...)
La cellule détecte les signaux dentrée de différente intensité dans
nimporte quelle ordre et calcule le seuil de commutation optimale.
*Vous pouvez également procéder dans lordre inverse: mesurer dabord sans
objet, ensuite avec lobjet.
Si le réglage du seuil de commutation nest pas possible (p. ex.
le signal de lobjet et le signal de larrière-plan ont presque la
même intensité), la rampe de LED clignote après l’étage de
réglage no. 3. Ensuite la cellule passe au mode fonctionnement
sans changer le seuil de commutation.
20
out
on
out
on out
on
out
on
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
out
on
delay
auto range
manual range
90
70
50
30
10
ms
400
200
150
100
50
%
1
3
2
Placer lobjet dans le faiscau
optique.*
Enlever lobjet du faiscau
optique.*
Appuyer une fois.
Appuyer une fois.
Les LED jaune et verte
clignotent
alternativement
(= la cellule est en mode
programmation).
Les LED jaune et verte
s’éteignent brièvement,
ensuite elles clignotent
de nouveau
alternativement.
Les LED jaune et verte
s’éteignent brièvement,
ensuite la LED verte
sallume
(= la cellule est en
mode fonctionnement).
F4
Appuyer jusqu’à ce
que la rampe de LED clignote.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

IFM OB5014 Installationsanleitung

Typ
Installationsanleitung
Dieses Handbuch ist auch geeignet für

in anderen Sprachen